JYZ-FF Overhead Line Remote Fault Indicators is usually used in 5~38KV (can be customized by 44KV, 69KV and 110KV ) overhead line power distribution network to monitor and detect short- circuit and earth fault. The fault signal is indicated by mechanical flag and three ultra-bright blinking LEDs with 360º sight. The fault information and current value can also be uploaded to the SCADA by 2.5G/3G/4G networks. |
This Overhead Line Remote Fault indicator can be mounted under live conditions with the help of an adapter and a hot stick. The parameters such as trip current, reset time, blinking interval, etc., can be read and adjusted by a bidirectional wireless tool. Battery low warning can be distinguished and indicated locally by red mechanical flag |
The earth-fault and short-circuit Fault indicator type JYZ-FF consists of:
1) 1 pcs DCU: Transmission fault and load current value to SCADA |
2) 3 pc indicators: short-circuit and earth fault detection and indication |
Subject | Value |
Short-circuit Fault | Indication of short-circuit fault by red mechanical flag and three ultra-bright blinking LEDs. |
Earth-fault | Indication of earth-fault by red mechanical flag and three ultra-bright blinking LEDs. |
Low Battery Warning | Indication of Low battery warning by red mechanical flag. |
Parameter Adjusted | The parameters can be read and adjusted by bidirectional wireless tools. |
Remote Transmission | DCU can transmit data to remote SCADA system. |
Power Supply | The indicator can take power from overhead lines, with lithium battery backup. The DCU can take power from solar energy with lithium battery backup. |
Subject | Value |
Short-circuit trip Current (Phase to Phase) | adjustable, 1A step, 150A default |
Earth-fault Voltage Drop (Phase to Ground) | adjustable: 1% step, 30% default |
Earth-fault Response Delay | adjustable: 1 second step, 30s default.<1kg |
Indication Unit Reset | 1 Manual by magnet 2 Communications by wireless tools or DCU (optional) 3 Time reset: adjustable, 1 second step, 24h default 4 Auto delay reset after repower, 1 second step, 30s default |
Protection Class | IP68 |
Internal Type Test | According to IEEE495-2007 |
Operation Temperature Range | -40~+70℃ |
Power Supply | Lithium battery type AA 3.6V / 2700mAh, replaceable |
Battery Life | Approx. 10 years |
Weight | <1kg |
Dimensions | Diameter: 93mm Height: 170mm |
Accuracy | 0A~300A ±3A 300A~800A ±1% |
Cable Diameter Ranges | 6mm~42mm |
Blinking Frequency | 20 per minute, adjustable |
Maximum Operating Voltage | <= 38KV |
Current Withstand | 31.5KA/2s |
Communication | 433MHz from indicators to DCU 2G/3G/4G from DCU to SCADA |