Subject | Value |
Short-circuit Trip Current (Phase to Phase) |
50~1200A adjustable, 1A step, 150A default |
Electrical filed drop record threshold | Adjustable: 1% step, 30% default |
Current record threshold | adjustable, 1A step, 5A default (≥5A) |
Current wave upload threshold | adjustable, 1A step, 50A default |
Indication Unit Reset | 1. remote reset through SCADA system 2. time reset: adjustable, 1 second step, 24h default, max. 48h 3. Auto delay reset after repower, 1 second step, 30s default max 5min, only for permanent fault |
Protection Class | IP68 |
Internal Type Test | According to IEEE495-2007 |
Operation Temperature Range | -40~+70℃ |
Indicator Battery | Lithium battery type AA 3.6V / 9Ah, replaceable |
Battery Life | 10 years |
Indicator weight | approx. 1kg |
DCU weight | <5kg |
Dimensions | Diameter: 114mm Height: 176mm |
Accuracy | 0A~300A ±3A 300A~800A ±1% |
Cable Diameter Ranges |
6mm~42mm |
Blinking Frequency | 10 per minute, adjustable |
Max. load/fault current | 1200A |
Voltage range | 5~38KV, can be customized to 44KV, 69KV and 110KV |
Current withstand | 31.5KA/4s |
Communication | 433MHz from indicators to DCU 2.5G/3G/4G from DCU to SCADA |
Communication Protocol | Indicator to DCU: private DCU to SCADA: IEC101, IEC104, DNP3.0,Modbus |
Waveform file format | COMTRADE 1999, including Ua, Ub, Uc, Ia, Ib, Ic, Io |