Features |
Short circuit Fault:Red mechanical flag and three red ultra-bright blinking LEDs.
|
Earth-fault:Red mechanical flag and three red ultra-bright blinking LEDs |
Low Battery Warning: Red mechanical flag. |
Parameter Adjust:The parameters can be adjusted by dial switches during production. |
Power Supply:Lithium battery, type AA 2.7Ah/3.6V.
|
Subject | Value |
Short-circuit Trip Current (Phase to Phase) | 150A, 300A, 450A, 600A, can be set by dial switch during production |
Trip Current Delay | 40, 80, 120, 200ms, can be set during production |
Indication Unit Reset |
|
Protection Class | IP68 |
Internal Type Test | According to IEEE495-2007 |
Operation Temperature Range |
-40~+70℃ |
Power Supply | Lithium battery type AA 3.6V/2.7Ah, replaceable |
Battery Life | 10 years |
Weight | Approx. 600g |
Dimensions | Diameter: 93mm Height: 128mm |
Accuracy |
0A~300A ±3A 300A~800A ±1% |
Cable Diameter Ranges |
6mm~42mm |
Blinking Frequency | 10 per minute, adjustable |
Max. load/fault Current | 1100A |
Voltage range | 5~14KV. For higher voltage, can be customized |
Current withstand | 31.5KA/4s |